FEATURES
Design life: 5 years
Robust plate for extended life.
Flame-arresting one-way pressure-relief vent for safety and long life.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to99% and freedom from electrolyte maintenance.
UL-recognized component.
Multicell design for economy of installation and maintenance.
Can be used in any orientation. Upright,side, or end mounting recommended.
Not restricted for air transport – Complies with IATA/ICAO Special Provision A67.
Not restricted for surface transport –classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189
Not restricted for water transport –classified as non-hazardous material perIMDG Amendment 27
Computer designed lead, low Calcium alloy grid for minimal gassing and ease of recycling.
Technical Specifications | |
Accessories | Inter unit connectors, racks and cabinet systems are available. |
Container materials | ABS (UL-94 HB) |
Equalization and cycle service charging voltage | 14.4 to 14.8VDC/unit Average at 77°F (25°C). |
Float charging voltage | 13.65 0.15 VDC/unit Average at 77F (25C) |
Maximum ac ripple (charger) | 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Maximum voltage allowed = 1.4% RMS (4% P-P). Maximum current allowed = 5.10 amperes RMS (C/20). |
Operating temperature range | Discharge: -20℃to 60℃ Charge: 0℃to 50℃ (with temperature compensation) |
Recommended maximum charging current limit | C/5 amperes @ 20 hr. rate. |
Recommended operating temperature range | +74°F (23°C) to +80°F (27°C). |
Self discharge | Batteries may be stored for up to 6 months at 77°F (25°C) and then a freshening charge is required. For higher temperatures the time interval will be shorter. |
Terminal | “L”terminal with 5.5mmclearance hole to accept 5mmbolt. |